New Construction - 1500 Frankford - Call Your Mother Deli
- Install owner supplied 3 phase panels A2 and A3 panel board MLO , both 125 A 120/208 V deriving from the EXISTING 400 A MCB panel already in the building .
- Wiring of all new equipment including Make Up Air, dish washer, oven, toasters and all other equipment included on the plans provided with sized breakers and disconnecting means included on the plans. - Air condensers HP1- . HP-2 and HP.3 are noted as existing and to remain with their wire sizing and existing disconnects.
- Wiring of new heating and Air conditioning units with disconnects by the prints.
- Wiring of the prep kitchen, washing area , dining area ,waiting area and all other rooms according to the plans - All outlets rated 150 A to ground shall be GFCI protected . Coordination with GC is needed to provide location for readily accessible GFCI protection for outlets behind equipment. - Wiring of the roof equipment by us with rated disconnects.
- Lighting circuits by the plans . Dimmers as noted on the plans - no dimming panel - Maestro dimmers only.
- Wiring of standard exit and emergency lights supplied and installed by us with night lights (always on) as shown on the plans - Installation of owner supplied 2 x 2 lay-in LED lights on the drop ceiling, all other light fixtures to be supplied by the owner .
- Wiring of all the outlets shown on the prints.
- Wiring of the walking cooler motor and light on site by us. - Wiring of the kitchen exhaust fans by the plans .
- 80A 3 phase 120/208v dishwasher line with disconnect.
Installation shall comply with 2017 NEC.